from datetime import timedelta
import pandas as pd
from faults import FaultConditionTen
from reports import FaultCodeTenReport
from utils import custom_arg_parser, save_report, describe_dataset
# python 3.10 on Windows 10
# py .\fc10.py -i ./ahu_data/MZVAV-1.csv -o MZVAV-1_fc10_report
# py .\fc10.py -i ./ahu_data/MZVAV-2-1.csv -o MZVAV-2-1_fc10_report
# py .\fc10.py -i ./ahu_data/MZVAV-2-2.csv -o MZVAV-2-2_fc10_report
if __name__ == '__main__':
args = custom_arg_parser()
# ADJUST this param for the AHU MIN OA damper stp
AHU_MIN_OA = 20
# G36 params shouldn't need adjusting
# error threshold parameters
OAT_DEGF_ERR_THRES = 5
MAT_DEGF_ERR_THRES = 5
var_dict = {
"mat_col": "AHU: Mixed Air Temperature",
"oat_col": "AHU: Outdoor Air Temperature",
"clg_col": "AHU: Cooling Coil Valve Control Signal",
"economizer_sig_col": "AHU: Outdoor Air Damper Control Signal",
"fan_vfd_speed_col": "AHU: Supply Air Fan Speed Control Signal"
}
_fc10 = FaultConditionTen(
oat_err_thres=OAT_DEGF_ERR_THRES,
mat_err_thres=MAT_DEGF_ERR_THRES,
oat_col=var_dict["oat_col"],
mat_col=var_dict["mat_col"],
clg_col=var_dict["clg_col"],
economizer_sig_col=var_dict["economizer_sig_col"]
)
_fc10_report = FaultCodeTenReport(
oat_col=var_dict["oat_col"],
mat_col=var_dict["mat_col"],
clg_col=var_dict["clg_col"],
economizer_sig_col=var_dict["economizer_sig_col"],
fan_vfd_speed_col=var_dict["fan_vfd_speed_col"]
)
df = pd.read_csv(args.input, index_col="Date", parse_dates=True).rolling(timedelta(minutes=5)).mean()
# describe dataset printing some stuff
describe_dataset(df)
# return a whole new dataframe with fault flag as new col
df2 = _fc10.apply(df)
print(df2.head())
print(df2.describe())
save_report(args, df, _fc10_report)