The Emerson ControlWave 'Next Generation' RTUs through...
High severity
Unreviewed
Published
Aug 18, 2022
to the GitHub Advisory Database
•
Updated Feb 1, 2023
Description
Published by the National Vulnerability Database
Aug 17, 2022
Published to the GitHub Advisory Database
Aug 18, 2022
Last updated
Feb 1, 2023
The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.